Test and tag requirements in NZ

Last reviewed 11 November 2026.

Test and tag is not compulsory in New Zealand. The law requires that electrical equipment is safe and kept safe; it does not say how you prove it. What the law does give you is a shortcut: under regulation 26 of the Electricity (Safety) Regulations 2010, an appliance used by your employees or contractors is deemed electrically safe if it carries a current tag issued under AS/NZS 3760. For hire, lease and rental equipment there is a second shortcut, an RCD. So the real question is not "must I?" but "how will I show this gear is safe if something goes wrong?". The table below answers that for each situation, followed by a worked example and a checklist you can print.

Scope. Plug-in appliances, leads and hand-held tools in New Zealand. Not fixed wiring, prescribed electrical work, or electrical medical devices (regulation 26 excludes them; regulation 25 points medical locations to AS/NZS 3551 and related standards). For Australia, see test and tag requirements in Australia, where the rules are different.

What the regulations actually say

Three provisions do the work. All quotations are from the Electricity (Safety) Regulations 2010 (version as at 2 October 2026) and the Health and Safety at Work Act 2015, both read on 11 November 2026.

WorkSafe New Zealand (page updated 16 October 2026) puts it plainly: testing and tagging is "one useful way" to check equipment, "However, it's not mandatory", and it is "up to the person conducting the business or undertaking (PCBU) to decide whether to test and tag."

Which route fits your situation

Your situationWhat the law requiresWays to show it
Employer or contractor: staff use your appliances at workDo not use or allow use of unsafe gear (reg 15(1)); safe plant (HSWA s36)A current AS/NZS 3760 tag is deemed safe (reg 26(2)). Without tags, you need another documented way: regular visual checks, maintenance records, RCD protection.
Hire or lease companyNot unsafe at the start of each hire (reg 15(1A))A current tag, or supply through a portable RCD or an RCD-protected circuit when first handed over (reg 26(3)).
Landlord supplying appliances in a rentalNot unsafe at the start of the tenancy (reg 15(1A))As for hire: a current tag, or RCD protection when the tenant first gets the appliance (reg 26(3)).
Construction or demolition siteInstallation periodically assessed under AS/NZS 3012 (reg 75(1)(c))Equipment complying with and used under AS/NZS 3012 is deemed safe (reg 25(d)). Site practice follows that standard, not this table.
Electrical medical devicesOutside regulation 26AS/NZS 3551 programs (reg 25(a)); ask your biomedical engineering provider.
Your own appliances at homeNot a workplace or a hireNo tagging duty. Look at cords and plugs; use an RCD outdoors.

Our decision rule, from the table: if other people use your gear for work, hire it or live with it, choose a route on purpose and write it down. Tagging is the route with a legal presumption behind it. For hire and rental, an RCD at handover is an equal alternative in the regulation. Doing nothing is not a route.

Who can do the testing

WorkSafe says the tester "doesn't need to be a registered electrical worker but the person needs to be able to understand the Standards involved", and that "only a registered electrical worker will be able to fix any problems the testing reveals." You can buy a tester and train a staff member, or hire a third party. Either way, a fail goes to an electrician, not back on the shelf.

How often

New Zealand's regulations set no retest interval for portable appliances, and WorkSafe publishes no table. If you rely on regulation 26, the tag has to be "current", which means retested on the schedule in AS/NZS 3760:2022 for that environment. WorkSafe's only example is that construction gear "outside and in damp conditions" needs testing more often than "a computer in an office". The intervals Australian regulators publish from the same standard (3 months on construction sites and for hire gear, 6 months in factories and workshops, 12 months or longer in low-risk offices) are set out on our AS/NZS 3760 retest intervals page; check them against your copy of the standard (Standards New Zealand).

How New Zealand differs from Australia

PointAustralia (model WHS states)New Zealand
Is testing mandatory?Yes in a hostile operating environment (WHS reg 150)No; a current tag is one way to be deemed safe (reg 26)
"Hostile operating environment"Defined, and triggers testingNot a concept in the NZ regulations
Record fields set by lawTester, date, outcome, next date (WHS reg 150(3))None in the regulations; the tag must be issued under AS/NZS 3760
Hire and rentalGeneral duties; regulator guidanceSpecific rule: safe at start of hire, tag or RCD (regs 15(1A), 26(3))
StandardBoth use AS/NZS 3760:2022, and AS/NZS 3012 on construction sites

So an Australian test and tag program works in New Zealand, but Australian advice about what is "required" does not carry across. More on the Australian side: how often you need to test and tag.

Worked example: a café that also lets a flat

An illustrative Wellington café owner has 12 plug-in items used by staff (kettle, toaster, two blenders, a stick mixer, microwave, a pie warmer, a vacuum, two extension leads, a laptop and a radio) and lets a furnished flat upstairs with a fridge, a heater and a microwave.

Printable checklist

DoneStep
☐List every plug-in item other people use for work, hire or live with.
☐Mark each: staff use, hire or lease, rental, construction site, medical, fixed.
☐Take fixed and medical items off the list; they have their own rules.
☐Choose a route per group: AS/NZS 3760 tag, or (hire and rental only) RCD at handover.
☐Decide who tests: a trained staff member or a third party, and how often under AS/NZS 3760.
☐Withdraw any failed item until a registered electrical worker repairs it.
☐Look at cords, plugs and tools between tests, as WorkSafe advises.
☐Keep one register of what was done, when, by whom and when it is next due.

A ready-made layout for the last step is our test and tag register template.

Keeping the dates

If you test for several New Zealand clients, TagVault keeps each client's register, sets the next due date from the item's environment when a pass is saved, and its interval rules can differ by jurisdiction. It is on Android in Australia and New Zealand. It does not read your tester, and it does not decide whether a client needs to test at all.

Get TagVault on Google Play

Questions

Is test and tag a legal requirement in New Zealand?

No. WorkSafe says it is "not mandatory"; the requirement is that equipment is electrically safe and kept that way. A current AS/NZS 3760 tag is one way to be deemed safe (regulation 26).

Who can test and tag in NZ?

Anyone with the knowledge and skills to do it correctly and understand the Standards; they need not be a registered electrical worker. Repairs do need one.

How often do you test and tag in NZ?

The regulations set no interval. A tag is only "current" if the item is retested on the AS/NZS 3760:2022 schedule for its environment; see our retest intervals page.

Do landlords in NZ have to test and tag appliances?

Not in those words. Appliances must not be electrically unsafe at the start of the tenancy (regulation 15(1A)). A current tag, or RCD protection when the tenant first gets the appliance, makes them deemed safe (regulation 26(3)).

When this page does not apply

TagVault keeps records to support your AS/NZS 3760 program. It does not confer competency or licensing, and it does not determine whether you or your client meet any legal obligation. The quotations above are from the New Zealand legislation and WorkSafe pages linked, read on the review date. The café in the example is illustrative.