Class 1 vs Class 2 appliances: what changes when you test and tag

Last reviewed 16 November 2026.

A Class 1 (Class I) appliance is earthed: its metal parts connect to the earth pin, and that earth is what protects you if something inside fails. A Class 2 (Class II) appliance is double insulated: two layers of insulation, or one reinforced layer, stand between the live parts and anything you can touch, so it has no earth. You tell them apart from the rating plate: Class II carries a square inside a square . For test and tag, Class I gets an earth continuity test and Class II does not; both get the visual inspection and an insulation or leakage test. The interval is the same for both everywhere except Queensland manufacturing and amusement work, where double insulated items go a year instead of six months. Below: a decision rule, the test table, a worked Queensland example and a check sheet to print.

Scope. Australian workplaces under AS/NZS 3760:2022. For New Zealand law see test and tag requirements in NZ. Construction sites follow AS/NZS 3012 as well. Medical equipment in patient areas is outside AS/NZS 3760.

The two classes in plain words

Class I (earthed)Class II (double insulated)
How it protects youBasic insulation plus a protective earth. If a live wire touches the metal case, current flows to earth and the fuse, breaker or RCD cuts the supply.Two independent layers of insulation, or reinforced insulation. No earth is needed or provided.
MarkingUsually none. Some carry an earth symbol at the earth terminal.The double-square symbol (IEC 60417 symbol 5172), often with the words "double insulated".
PlugThree-pin, earth pin connected.Usually two-pin. Some have a three-pin plug or IEC connector; go by the rating plate, not the plug.
Typical itemsKettles, toasters, microwaves, fridges, bench grinders, metal-cased heaters, desktop PCs with a three-pin lead.Most hand-held power tools, hair dryers and straighteners, phone and laptop chargers, many lamps.

The typical items are a guide only. Two drills on the same shelf can be different classes, which is why the plate decides.

How to tell, item by item

  1. Find the rating plate (the sticker or moulded label with volts and watts). Double-square symbol or the words "Class II" or "double insulated": it is Class II.
  2. No symbol, three-pin plug: treat it as Class I.
  3. No symbol, two-pin plug, mains voltage: stop. A mains item with no earth and no double-insulation mark is not something to pass; get a competent person to look at it.
  4. Plate missing or worn off: treat it as Class I and test the earth. If an item you are treating as Class I has no earth continuity, it fails. Take it out of service.
  5. Runs on a plug pack or charger (12 V lights, laptops): the plug pack is the mains item, and it is usually Class II; check its own plate. The low-voltage side is not tested as a mains appliance.
  6. Write the class in the register so the next tester does not have to work it out again. Our register template has a column for it.

Which tests each class gets

WorkSafe Queensland's test and tag course page lists the competencies AS/NZS 3760 expects of a tester. One of them is "the ability to distinguish between electrical equipment that is double insulated and equipment that is protectively earthed and identify the appropriate test for each type." In practice:

StepClass IClass II
Visual inspection (case, cord, plug, anchorage, guards, vents)YesYes. Look hard at the case: a cracked shell on a double-insulated tool removes a layer of protection.
Earth continuity, flexing the cord along its length (AS/NZS 3760 Appendix A, per WorkSafe Queensland)Yes, from the plug's earth pin to exposed metalNo: there is no protective earth to measure
Insulation resistanceYes, live parts to earthYes, live parts to any accessible metal (a chuck, a blade guard, screws)
Leakage current (an alternative where an insulation test is not suitable, for example equipment that must be switched on to test)YesYes

The pass limits are in AS/NZS 3760:2022's tables for leakage current and insulation resistance. The standard is sold, not free, and we have not reproduced figures we cannot check against it here. Your tester's instrument applies them when you pick the class, so picking the wrong class is the mistake to avoid: testing a Class II drill as Class I fails it on earth continuity it never had, and testing a Class I kettle as Class II skips the one test that checks its main protection.

The WorkSafe WA code of practice describes the same work in general terms: inspection for damage and discolouration, "checking the integrity of protective earth and insulation resistance", cord anchorage, controls, guards and plug rating.

Does the class change how often you test?

Outside Queensland, no. Under regulation 150 of the model WHS Regulations the duty to test turns on the environment, and the regulator tables set intervals by environment. See how often to test and tag and what counts as a hostile operating environment.

In Queensland, sometimes. The Electrical Safety Regulation 2026 (in force 1 September 2026) splits two kinds of work by class:

Type of work (Qld)Not double insulated (Class I)Double insulated (Class II)Section
Manufacturing workAt least every 6 monthsAt least once every year133
Amusement workAt least every 6 months, plus a safety switchAt least once every year, plus a safety switch128
Service work, office work, construction, ruralNo class difference: see how often to test and tag138, 140, 141

Worked example: a Queensland fabrication shop

A small steel fabrication shop in Toowoomba is doing manufacturing work. Its plug-in gear: a bench grinder, a drill press and a mig welder (3 earthed items), and 5 angle grinders, 3 drills and 2 heat guns marked with the double square (10 double-insulated items).

ItemsInterval (s 133)Tests a year
Class I36 months6
Class II1012 months10
Total1316

Putting everything on 6 months instead would mean 26 tests a year. That is allowed (shorter is never non-compliant) and some shops choose it so there is one date to remember. What is not allowed is the reverse: a Class I grinder on the 12-month cycle because it sat on the shelf with the Class II ones.

Class check sheet to print

Use your browser's Print on this page; the navigation is left off.

Tag no.ItemDouble square? (Y/N)Plug (2/3 pin)Class recordedEarth test done? (Class I)Interval

Rule: no double square = Class I. Two-pin plug and no double square on a mains item = do not pass. Checked by: ____________ Date: ________

Recording the class

TagVault records each item as Class I, Class II, a lead, an RCD or a portable outlet device, alongside its test results, so the class is on file when the next test comes round. Its built-in intervals are set by environment and do not yet split Queensland's double-insulated rows, so a Queensland workshop should check the due date on its Class II items. It is optional; the sheet above does the same job on paper.

Get TagVault on Google Play

Questions

What is the difference between a Class 1 and a Class 2 appliance?

Class 1 relies on a protective earth. Class 2 is double insulated and has no earth. The double-square symbol on the plate marks Class 2.

Does a Class 2 appliance need an earth continuity test?

No. There is no earth to measure. It still gets the visual inspection and an insulation or leakage test.

Do Class 1 and Class 2 appliances have different test and tag intervals?

Only in Queensland manufacturing and amusement work: 6 months for Class I, a year for Class II.

What if an appliance has no class marking?

Treat it as Class I and test the earth. No earth continuity on a three-pin item means it fails.

When this page does not apply

TagVault keeps records to support your AS/NZS 3760 program. It does not confer competency or licensing, and it does not determine whether you or your client meet any legal obligation. The quotations above are from the regulator and legislation pages linked, read on the review date. The fabrication shop in the example is illustrative.